24/7 Standby · Always At Your Service 💬 WhatsApp +65 8989 2833

Where Each Appliance Goes Under the Hood: Planning the Cooking Line Before the Kitchen Exhaust Is Drawn

22 Nov 2026 · Design & Build

Where Each Appliance Goes Under the Hood: Planning the Cooking Line Before the Kitchen Exhaust Is Drawn
Give the exhaust designer the final list of appliances and their positions before the hood is drawn. Put the heaviest-duty appliances (wok burners, char-grills, fryers) inside the hood with full overhang, away from the ends, doors and air outlets; group appliances of similar duty so the hood can be zoned; keep the fryer from sitting hard against an open flame; give charcoal its own extract and keep wash-up steam out of the cooking hood; keep filters and access panels reachable; and design the suppression nozzles and gas shut-off to the same line, with a slot for future equipment.

Pictured above: two new stainless hoods going up at an F&B kitchen fit-out, from BC Air’s Live Jobs page, with the ductwork rising into the ceiling void. The cooking line is not under them yet. That is the point of this post: by the time a hood is hung, where each appliance will stand should already be settled, because the hood was drawn around that list.

Most new kitchens are planned in this order: the menu, then the equipment layout, then the exhaust, drawn last around whatever the layout shows. But the order of the appliances along the line decides much of how well the hood captures, how hard the fan works, where the suppression nozzles go and how easy the system is to clean. Once the hood is fabricated, moving an appliance a metre is no longer a small change.

This post is for the owner, the operations person or the fit-out manager looking at a draft kitchen layout for a new outlet in Singapore. It sets out the decisions about the cooking line that are worth settling before the exhaust is drawn, and the questions to ask. It gives no price: a commercial kitchen ventilation system is quoted after we have seen the layout and the cooking line.

The short answer

Give the exhaust designer the final list of appliances and where each one will stand before the hood is drawn. Put the heaviest-duty appliances, such as wok burners, char-grills and fryers, where the hood captures best: inside the hood with full overhang around them, not on the last metre at either end and not beside a door, a pass-through or an air-conditioning outlet. Group appliances of similar duty together so the hood can be zoned if it needs to be, keep the fryer from sitting hard against an open flame, give charcoal its own extract, keep wash-up steam out of the cooking hood, and leave every filter, grease cup and access panel reachable. Then have the fire suppression coverage and the gas shut-off designed to that same line, and leave room on the drawing for what you might add later.

Why the order matters at all

A hood is not sized for a kitchen. It is sized for a list of appliances in particular positions, because each one throws off a different amount of heat, grease and smoke. We explain that process in how we size a kitchen exhaust hood for your cooking line. A wok burner sends up a large, fast plume; a steamer a gentle one. The same appliances in a different order can need a different hood, a different extract rate, or a hood split into sections.

You can see the effect in a kitchen that has been running for a while. Pull the filters out of a long hood and the ones over the wok are black while the ones at the far end look almost clean. That pattern, and what it tells you, is in uneven grease across a long kitchen hood. The order of the line is what sets it in the first place.

1. The heaviest duty goes where the hood captures best

A hood captures best where the plume rises well inside its edges, with overhang on every open side. On a long hood the pull is not the same at every point, and the last stretch at each end is where a strong plume is most likely to spill. So, as a rule of planning:

  • Keep the wok range, char-grill and fryers inside the hood with full overhang around them, not pushed to the very end of the line where one side has little margin.
  • Put the lighter appliances, such as a bain-marie, a steamer or a holding unit, towards the ends if they have to share the hood.
  • Keep the heavy appliances away from doors, pass-throughs and air-conditioning or supply air outlets. A cross-draught pushes the plume sideways before the hood can take it. The same effect from a pedestal fan or an air-con blowing across the line is covered in a fan or air-con blowing across the cooking line.

2. Group appliances of similar duty

A line that alternates heavy and light appliances, wok, steamer, fryer, bain-marie, grill, forces one hood to be sized for the heaviest plume along its whole length. Where the heavy appliances sit together, the hood can be zoned: a section with more extract over the heavy group and less over the light group, or two hood sections instead of one long canopy. If the drawing mixes heavy and light appliances, ask whether regrouping them would give a simpler or smaller system before the layout is fixed.

3. The fryer and the open flame

A fryer next to an open-flame burner is a common sight and a real risk: hot oil can splash onto a flame, and a fryer fire is exactly what kitchen fire suppression systems exist for. Many kitchens keep the fryer from sitting hard against an open burner, with a gap or a steel splash guard between them. How much separation your line needs is settled by the equipment supplier’s installation instructions and the fire suppression designer, not by the person drawing the floor plan. Raise it on the drawing, because the answer changes the length of the line, and the length of the line changes the hood.

4. Charcoal and wood get their own extract

A charcoal grill, a tandoor or a wood-fired oven produces embers and a different kind of smoke from a gas line. In the kitchens we design, a solid-fuel appliance normally gets its own extract arrangement rather than sharing a hood and duct with the gas line. The reasons are in charcoal grills, tandoors and wood-fired ovens. If one is on the menu, it should be on the layout as a separate item from the start, not slotted into a gap in the gas line.

5. Steam belongs somewhere else

The dish machine and pot wash are often drawn close to the cooking line to save steps. Their steam is a different load from cooking grease, and putting it under the cooking hood mixes moisture into a greasy duct. Where possible, the wash-up area gets its own steam extraction, covered in the wash-up area nobody ventilates. Combi ovens and steamers on the line itself are a cooking load and belong under a hood, but they suit the lighter end of it.

6. Tall appliances, oven doors and the salamander

  • Height. A tall stockpot range, or a salamander mounted above the line, changes the distance between the cooking surface and the filters, and that distance is part of the hood design. Give the designer the height of each appliance, not just its footprint.
  • Oven doors. An oven releases heat and vapour forward when its door opens. The front overhang has to allow for that, and an oven pushed to the end of the hood can release its heat outside it. The roast-meat version of this problem is in roast meat shops and the hot oven door.

7. Leave the filters, grease cups and access panels reachable

Baffle filters come out to be washed, usually nightly in a busy kitchen, and a crew member has to be able to lift each one down from the floor or a proper step. A tall appliance placed in front of the filter bank, or a line pushed so far back that the filters are out of reach, means the filters do not come out as often as they should. The same applies to the grease cup and to the duct access panels behind and above the hood. What to settle about the filters themselves is in baffle filter design before the hood is fabricated.

8. Suppression nozzles and the gas shut-off follow the line

A kitchen hood fire suppression system has nozzles aimed at particular appliances in particular positions. It is not a general blanket over the line. That means the suppression design can only be finished once the line order is final, and any later move of an appliance is a reason to have the coverage reviewed. The gas supply, the shut-off and any interlock with the exhaust fan are planned around the same line; the wiring side is in hood, fan, gas and suppression interlocks. We install suppression as part of the same project when you ask for it; our scope is on the fire suppression systems page.

9. Leave a slot for what you might add

A common call on a running kitchen is about equipment added after opening, such as a second fryer at the end of the line. If there is any chance of that, say so now: a hood that already allows for one more appliance, in a position the suppression design knows about, is a far smaller job later than a hood extension. What happens when that is not planned is in adding cooking equipment to an existing kitchen hood.

Questions to put to the layout and the exhaust designer

  1. Is this the final list of appliances, with the duty and height of each, and is it the list the hood is being drawn to?
  2. Do the heaviest appliances sit inside the hood with full overhang, away from the ends, doors and air outlets?
  3. Would grouping the heavy and light appliances allow a zoned or smaller hood?
  4. What separation does the fryer need from any open flame, and who has confirmed it?
  5. Is any solid-fuel appliance on its own extract, and is the wash-up steam kept out of the cooking hood?
  6. Can every filter, grease cup and access panel be reached once the appliances are in?
  7. Are the suppression nozzles and the gas shut-off drawn to this exact line, and is there a slot for a future appliance?

How we handle it

We design and build commercial kitchen exhaust and ventilation systems in-house, from the hood and the ductwork to the fan, make-up air and controls, and the hoods are fabricated in our own workshop. The whole system is described on our commercial kitchen exhaust and ventilation systems page and the design side on design and build. Where the layout is unusual and you want to see how the air will move before anything is built, our CFD modelling and air balancing page explains what a study covers.

If you are looking at a draft layout for a new kitchen, WhatsApp BC Air on 8989 2833 with the location, the appliances planned for the line, its approximate length, whether it is a new fit-out or an existing kitchen, and when you need it ready. A copy of the kitchen layout helps more than anything else. We are on 24/7 standby, and we quote after seeing the layout and the cooking line.

Related reading: how we size a hood for the cooking line · adding equipment to an existing hood · uneven grease across a long hood

Questions

Common questions

Where should the wok burner and fryer go under a long kitchen hood?
Inside the hood with full overhang around them, not on the last stretch at either end, and away from doors, pass-throughs and air-conditioning or supply air outlets. The ends of a long hood are where a strong plume is most likely to spill, so lighter appliances such as a bain-marie or a holding unit suit the ends better.
Should heavy and light cooking appliances be mixed along the line?
It is better to group appliances of similar duty. A line that alternates heavy and light appliances forces one hood to be sized for the heaviest plume along its whole length. Grouping the heavy appliances together lets the hood be zoned, or split into sections, with more extract where it is needed.
Can a fryer sit right next to a gas burner?
It is a common sight and a real risk, because hot oil can splash onto an open flame. Many kitchens keep a gap or a steel splash guard between them. The separation your line needs is set by the equipment supplier's installation instructions and the fire suppression designer, so raise it on the drawing before the hood is sized.
Does a charcoal grill or tandoor share the main kitchen hood?
In the kitchens BC Air designs, a charcoal or wood-fired appliance normally gets its own extract arrangement rather than sharing a hood and duct with the gas line, because it produces embers and a different kind of smoke. Show it on the layout as a separate item from the start.
What happens to the fire suppression system if we move an appliance later?
Suppression nozzles are aimed at particular appliances in particular positions, so moving, swapping or adding an appliance is a reason to have the coverage reviewed. That is why the suppression design should be finished only once the line order is final, and why it helps to leave a planned slot for any equipment you might add.
How much does a commercial kitchen ventilation system cost?
There is no fixed price, because the hood, duct, fan, make-up air and any suppression are sized to your cooking line and your unit. BC Air quotes after seeing the layout and the cooking line. Send the location, the planned appliances and the approximate line length on WhatsApp.

Need This Sorted in Your Kitchen?

We design, clean, repair and maintain commercial kitchen exhaust systems across Singapore — on 24/7 standby.

Chat on WhatsApp