Kitchen Exhaust in a Conservation Shophouse: Where the Ductwork Can Actually Go

25 Aug 2026 · Design & Build

Kitchen Exhaust in a Conservation Shophouse: Where the Ductwork Can Actually Go
In a Singapore conservation shophouse, plan on the exhaust discharging at the rear, because the conserved front facade is not a route for ductwork, cowls or fans. Then answer three questions before signing a lease: whether the rear discharge clears the surrounding occupancies rather than filling a shared light well with residential above, whose property the vertical riser passes through and whether that requires fire-rated ductwork, and whether the wall the duct is fixed to is a shared party wall. Expect the fan to need a designed structural support rather than brackets into existing masonry, expect vibration to travel further through timber and masonry than through concrete, and design make-up air in, because a deep narrow plan otherwise pulls replacement air the full length of the dining room and in under the front door.

A conservation shophouse is one of the most attractive units an operator can take in Singapore, and one of the hardest to put a commercial kitchen into. The rent reflects the address. The ventilation almost never reflects the menu.

The problem is not that a shophouse is old. It is that the four things a kitchen exhaust system needs — a route out, a discharge point far enough from people, structure that will carry a fan and a duct run, and replacement air coming in — are all constrained at once, and the constraints belong to different people.

The front elevation is not a route

Start with the obvious one, because it removes half the possibilities before you draw anything: on a conserved building the front façade is the thing being conserved. Ductwork, cowls, grilles and fans on the street elevation are not a design option to be negotiated late in the programme.

The specific guidelines that apply to your building, and the owner's position, are the authority here — confirm them before anything is designed rather than after. But plan on the working assumption that the extract goes out at the back, and treat anything else as a bonus.

That single assumption drives everything else, because most shophouses are deep and narrow with the kitchen wherever the previous fit-out put it. If the cooking line ends up at the front of a long unit, you have committed yourself to a long horizontal duct run through the whole building — and long horizontal runs are where grease collects, where access panels get omitted, and where duct routing quietly costs you extract performance.

The rear is the route, and it is crowded

The back of a shophouse is typically a small yard, a rear staircase, a light well or an alley shared with the units on either side. It is also where the neighbours' kitchen windows, air-conditioning condensers and toilet extracts already are.

Three questions decide whether the route works:

Does the discharge clear the surrounding occupancies, or does it point at them? A rear discharge that terminates at first-floor level in an enclosed light well does not disperse. It fills the well, and the well is shared with everyone above and either side. In a mixed-use street the floors above are often residential — which means an odour complaint is not a business dispute, it is a home. Our note on where odour complaints actually come from covers the discharge geometry that produces them.

Can the duct get to roof level, and through whose property? A vertical riser has to pass floors that may be a separate tenancy or a separate residence. Where the duct passes through another occupancy, the fire-rating question is no longer theoretical — see when kitchen exhaust ductwork has to be fire-rated. Establishing who controls the space the riser passes through, and getting that in writing, belongs at lease stage.

Is the rear wall yours? Shophouses are built in terraces and the side walls are party walls. Coring, bracketing or hanging a duct off a wall you share is not a decision one tenant makes alone.

Old structure carries loads differently

A commercial extract fan is a rotating mass, and the duct run full of grease is a static one. In a modern building both are hung off a concrete slab and nobody thinks about it.

In a shophouse the upper floors may be timber, the walls may be masonry of unknown condition, and the roof structure was designed for a roof rather than for plant. Two consequences follow, and both cost money when they are discovered late:

  • The fan needs a designed support, not brackets into whatever is there. This is a structural question with a structural answer, and on a conserved building it may need the building owner's consent as well.
  • Vibration travels further in an old building than in a new one. Timber and masonry transmit low-frequency hum through the structure into the units next door and above, and structure-borne noise is the complaint that is hardest to argue with and hardest to fix retrospectively. Noise and vibration complaints explains why the path matters more than the decibel reading.

Anti-vibration mounts, flexible connections and a support designed for the actual fan are cheap at design stage. They are disruptive to add once the kitchen is trading.

Where does the replacement air come from?

This is the one that catches shophouse operators hardest, because the plan form works against you. A deep narrow unit has an opening at the front and an opening at the back, and the front one is usually the dining room and the entrance.

Extract without designed make-up air pulls its replacement through the dining room and in under the front door. In a shophouse that means the cooking smell travels the full length of the space towards the customers, and the front door becomes heavy. It is a pressure problem, not a smell problem, and it has a design answer: make-up air and air balancing is where it is solved.

The complication in a conserved building is that the make-up air has to come in somewhere, and new external openings are exactly what conservation controls restrict. Which is another reason the ventilation strategy belongs in the lease decision rather than in the fit-out.

What was already there is evidence, not permission

Most conservation shophouses that come up have been F&B before. There is a hood, there is a duct, and there is a fan somewhere at the back. It is tempting to read that as proof that the route works.

It is proof that a route existed for a previous menu, at a previous volume, under whatever arrangement the previous operator had. It tells you nothing about whether it was ever approved, whether the neighbours tolerated it, or whether it will carry your cooking line. What to check in an existing kitchen exhaust when you take over a unit is the survey to run before you sign, and in a shophouse there is one extra question to put to the landlord: what approvals exist for the current system, and can I see them?

If the answer is that nobody has the paperwork, treat the existing installation as an unknown to be verified rather than as a starting point.

Grease, access and the cleaning you will actually be able to do

Long runs through an old building tend to be difficult to reach, and a duct you cannot reach is a duct that does not get cleaned. Grease accumulation in an inaccessible horizontal run is the single most serious fire risk in this type of unit, and it is a design decision made months before it becomes a problem.

Walk the intended route on the drawing and mark where access panels will go. If the run passes above a false ceiling in the dining room, that is where the panels have to be, and it is far better to know that while the ceiling is still a line on paper.

The sequence that works

  1. Before signing: establish where the exhaust can discharge, through whose property the riser passes, and what the building owner will permit. Get it in writing.
  2. Survey what exists and ask for its approval history rather than assuming it has one.
  3. Equipment schedule before layout. The cooking line sizes the extract; in a constrained unit it may also decide whether the menu is possible at all.
  4. Design extract, make-up air and the duct route as one thing, including the structural support for the fan.
  5. Mark access panels on the drawing, not on site.
  6. Commission and keep the record, because in a shared building you will one day need to show what the system was doing when it was new.

The honest summary

Some shophouse units cannot carry the kitchen the operator has in mind. That is a legitimate finding, and it is much cheaper to reach before a lease is signed than after a fit-out has started. A menu that works in a standalone unit with a clear roof route may not work in a terrace with residential above and a shared light well at the back.

The good news is that this is knowable in a morning. A survey of the unit, the rear elevation and the route to roof level answers most of it.

If you are looking at a shophouse now

Tell us the street, whether you have signed, what you intend to cook, and what is already in the unit. If the honest answer is that the route does not exist for that menu, we will say so while you still have the option of walking away.

BC Air is operated by WCT (S) Systems Pte Ltd. We do not publish prices for design and build work, because a meaningful figure depends on the cooking line, the duct route and the discharge point; we survey and quote against a scope.

Message us on WhatsApp about a shophouse unit, or see our kitchen exhaust design and build and commercial kitchen ventilation work.

Questions

Common questions

Can kitchen exhaust ductwork run on the front of a conservation shophouse?
Plan on the answer being no. On a conserved building the front facade is the thing being conserved, so ductwork, cowls, grilles and fans on the street elevation are not a design option to negotiate late in the programme. Confirm the guidelines that apply to your specific building and the owner's position before anything is designed, and work on the assumption that the extract goes out at the back.
Where does the exhaust discharge in a shophouse?
Usually at the rear, and that is where the difficulty starts. The back of a shophouse is typically a small yard, a rear staircase, a light well or a shared alley, and it already contains the neighbours' windows, condensers and toilet extracts. A discharge that terminates low in an enclosed light well does not disperse, it fills the well, and in a mixed-use street the floors above are often homes rather than businesses.
Why does vibration matter more in a shophouse than in a modern building?
Because the structure carries it differently. In a modern building the fan and duct hang off a concrete slab. In a shophouse the upper floors may be timber and the walls masonry of unknown condition, and both transmit low-frequency hum through the structure into the units next door and above. Structure-borne noise is the hardest complaint to argue with and the most disruptive to fix once the kitchen is trading, so anti-vibration mounts, flexible connections and a designed fan support belong in the design rather than in the remedial works.
Why is make-up air harder in a shophouse?
The plan form works against you. A deep narrow unit has an opening at the front and an opening at the back, and the front one is the entrance and the dining room. Extract without designed make-up air pulls its replacement the full length of the space and in under the front door, so cooking smell travels towards the customers and the door becomes heavy. The complication in a conserved building is that new external openings are exactly what conservation controls restrict, which is why the ventilation strategy belongs in the lease decision.
The unit already has a hood and duct. Does that mean the route is approved?
No. It is evidence that a route existed for a previous menu at a previous volume under whatever arrangement the previous operator had. It says nothing about whether it was approved, whether the neighbours tolerated it, or whether it will carry your cooking line. Ask the landlord what approvals exist for the current system and to see them; if nobody has the paperwork, treat the installation as an unknown to be verified rather than as a starting point.
What should be settled before signing a shophouse lease?
Where the exhaust can discharge, through whose property a vertical riser would pass, whether the wall the duct is fixed to is shared, and what the building owner will permit - all in writing. Then survey what exists and ask for its approval history. Some shophouse units cannot carry the kitchen an operator has in mind, and that is a legitimate finding, far cheaper to reach before a lease is signed than after a fit-out has started.