20 Nov 2026 · Design
A ventilation CFD study for a restaurant should include the kitchen, the dining room and the openings between them whenever the complaint is about smell, pressure, doors or air-conditioning. A hood-only model shows whether the canopy captures the plume but cannot explain why the dining room smells of the kitchen. The kitchen should sit slightly negative to the dining room. Ask for the door-open case, and ask who measures and balances the finished system. An existing kitchen that underperforms usually needs air balancing first.
Pictured above: the inside of a hood canopy on one of BC Air’s projects (Aljunied), looking up at the mesh-covered opening where the air leaves the hood. A photo from our own work, reused here because that opening is where the airflow the model has to describe goes in. It is the kitchen end of the story; the rest of this post is about the other end, the dining room.
Search for room ventilation CFD in Singapore and most of what comes back is about car parks, tunnels and smoke control. A restaurant is a different animal. The air that matters is not only the plume over the wok. It is also the air that moves between the kitchen and the dining room when the doors open, when the air-conditioning cycles, and when the exhaust pulls harder than the supply can follow.
So when an owner asks us to “model the kitchen”, the first thing we ask is where the model should stop. This post is about that question, because the answer decides whether the study explains your problem or only describes the hood.
CFD, computational fluid dynamics, models how air, heat and smoke move through a space on screen before anything is fabricated, or before a change is made to a kitchen that already exists. It lets airflow, capture velocity over the cooking line and the pressure balance between spaces be tested and refined while everything is still a drawing. The words that matter in that sentence are “between spaces”. A model that contains only the hood can say whether the canopy captures the plume. It cannot say why the dining room smells of the kitchen.
Every model has an edge: the walls and openings beyond which the study does not look. If the edge is the hood canopy, the air at the edge is whatever the person setting up the model assumed. Real kitchens do not get to assume. The air at that edge is the dining room’s air, being pulled through the pass, the open door or the gap under it, and it arrives at whatever speed and direction the pressure difference gives it. That is why we put three things inside the boundary on a restaurant job, not just the cooking line:
This is the part a hood-only model cannot see, and it is the part customers notice. A kitchen should sit slightly negative against the dining room, so that smell and smoke drift towards the hood and not towards the tables. Slightly less supply than exhaust is normally what you want. Too little supply and the kitchen goes strongly negative: doors become heavy or slam, gas flames lift and lean, the hood captures worse because the fan is working against a partial vacuum, and the dining room, which is often the only supplied space, becomes the kitchen’s replacement air. Too much supply and you push kitchen air into the dining room instead. There is a window between those two, and finding it is what air balancing does on site. A model inside the right boundary lets you look for the window on screen first, and see what a propped-open door or a change in the air-conditioning supply does to it.
1. The dining room smells of cooking while the exhaust is running. The hood may be perfectly good. The cause is often the pressure and the openings, not the canopy. We have a separate post on cooking smell in the dining area with the exhaust running; a model that includes the dining room is how you test the explanation before you spend money acting on it.
2. An open or show kitchen. When there is no wall between the cooking line and the guests, the dining room is not next door to the problem, it is the problem. The air-conditioning supply, the guests’ seating and the cooking line are one airflow picture. Leaving the dining room out of the model leaves out the thing the study was commissioned to protect.
3. A refit that moves a door, a pass or an appliance. Change one opening and the pressure between the two rooms changes with it. This is a design question again, even if the kitchen has been trading for years, and it is one of the cases we describe in when a CFD ventilation study is worth paying for.
Not every job needs it, and we would rather say so. If the kitchen is a sealed back-of-house room with a single door that is always shut, and the question is only whether a new hood will capture a new appliance, a model of the kitchen and its make-up air may answer it. And if the kitchen already exists and is underperforming, the usual first step is not a model at all. It is measuring what the system is doing, which is air balancing, and we cover that order of events in air balancing first or CFD first. Modelling comes in after, if the readings do not explain the cause.
Whoever you ask, put these to them before you agree the scope:
On the last point: we run the modelling ourselves rather than subcontracting it, so the team that models the airflow also designs the ductwork, builds it and balances it at commissioning, and a scenario can be re-run quickly when a layout changes. The model predicts; the balancing visit proves it. A model with no measurement behind it is still a prediction.
The floor plan should show the kitchen and the dining room, not only the kitchen, with every door and opening marked and a note of which are normally open. Add the position of the air-conditioning supply and return in the dining area, the list of appliances under each hood, and the exhaust and make-up air figures if anyone has set them. The fuller checklist is in what to send before a CFD quote, and how the finished system is measured is in make-up air and air balancing.
Our service page for this work is ventilation CFD modelling and air balancing. It is built for commercial kitchen and cooking-line ventilation, which is the ventilation we design, build, clean and maintain every day, aligned with NEA, SCDF, BCA and bizSAFE requirements. We quote each system individually, because the cooking line, the number of hoods, the duct run and the make-up air differ from kitchen to kitchen, so there is no fixed price to give here.
The short version:
WhatsApp BC Air with the location, whether the kitchen is on paper or already built, what is going wrong and a floor plan that shows the dining room as well as the kitchen. We are on 24/7 standby, and the quotation follows once we have seen the details.
Related reading: what to send before a CFD quote · when a CFD study is worth it · cooking smell in the dining area